Conference Paper
Proceedings of Building Simulation 2011: 12th Conference of IBPSA
Operation Strategies For An Office Building Integrated With Multi-Story Double Skin Facades In The Heating Season
Operation Strategies For An Office Building Integrated With Multi-Story Double Skin Facades In The Heating Season
Jae-Wan Joe, Won-Jun Choi, Jung-Ho HuhDOI: https://doi.org/10.26868/25222708.2011.1623Abstract: In this paper, heating energy saving strategies for winter are proposed for office buildings with a multistory double skin façade. Based on a model that was validated with measured data, two alternative operation strategies were analyzed. A model that introduces heated air in the cavity to the indoors by openable windows control(Case 2) and a model that combines it with HVAC by using a cavity as a preheating space(Case 3) were compared with the conventional model(Case 1). The results of the comparison showed that the Case 2 and 3 reduced the heating energy by about 3.4 and 37.9 % respectively. Pages: 1913 - 1919 Paper:![]()