Conference Paper

Proceedings of Building Simulation 2019: 16th Conference of IBPSA

     

Comparison and Verification of the Simulation Results of DeST Based on ASHARE Standard 140-2014

Yue Jiang 1, Xing Shi 1, Xin Zhou 1, Xing Jin 1, Jingjing An 2, Da Yan 2
1 SouthEast University, NanJing, People's Republic of China
2 Tsinghua University, BeiJing, People's Republic of China


DOI: https://doi.org/10.26868/25222708.2019.210956
Abstract: Based on the ASHRAE Standard 140-2014, this study takes the simulation results of DeST and other simulation software to comprehensively test the accuracy and validity of DeST in calculating building thermal loads and space cooling and heating equipment performance. Special cases were also designed to find out the influencing factors that led to results’ differences. It was found that the solar lost through the window, the setting of shading geometry and the mode of inputting surface coefficients can make a big difference to the simulation results. The calculation deviations in most ASHRAE-140 cases are within 10%, which indicate the accuracy of DeST in building energy simulation.
Keywords: DeST, inter-program comparison, ASHRAE Standard, program evaluation
Pages: 1506 - 1513
Paper: