Conference Paper

Proceedings of BSA Conference 2024: Sixth Conference of IBPSA-Italy

     

Modeling a Dew Point Indirect Evaporative Cooling System for TRNSYS Building Simulations: Proposal and Validation

Alessandra Urso, Gianpiero Evola, Francesco Nocera, Vincenzo Costanzo, Ana Tejero-Gonzales, Eloy Velasco-Gomez

DOI: https://doi.org/10.13124/9788860462022_14
Abstract: This paper aims to develop a mathematical model of a dew-point indirect evaporative cooler that can be easily implemented in a TRNSYS building simulation environment. The model is validated against experimental data from a tested mixed flow prototype. The results show that the model is consistent with the experiments with an error in the primary air temperature drop between 12% and 18%. Furthermore, a parametric analysis is performed to evaluate the effect of the size of the device. The temperature drop may double by increasing three times the height or the width of the device. In conclusion, this study reveals the importance of a proper calculation of the Nusselt Number, especially for the wet channel.
Pages: 105 - 112
Paper: