Conference Paper
Proceedings of eSim 2018: 10th Conference of IBPSA-Canada
The Limitations of Multi-Zone Infiltration Algorithms in Whole-Building Energy Simulation Engines
The Limitations of Multi-Zone Infiltration Algorithms in Whole-Building Energy Simulation Engines
Cara H. Lozinsky, Marianne F. TouchieAbstract: The algorithm used within EnergyPlus for multi-zone infiltration computations consists of a multivariable regression equation based on limited data collected from single-family homes, which do not accurately represent airflow patterns in MURBs. Depending on the coefficient scheme used with the regression equation, the resulting infiltration rates may or may not appropriately account for the effects of wind and/or air buoyancy. This paper compares the infiltration profiles for a 40-m and a 10-m building, calculated using three coefficient schemes recommended by EnergyPlus with the zone infiltration algorithm, and the theoretical infiltration profiles calculated from first principles using the Power Law Equation. The analysis was conducted for cities in each of North America’s eight climate zones. Depending on the coefficient scheme selected, the resulting infiltration profiles varied considerably, especially for the 40-m building in cold climate regions. These limitations need to be considered during model development, to ensure that infiltration is accurately accounted for. Keywords: building infiltration, whole-building energy simulation, calibrationPages: 367 - 374 Paper:![]()