Conference Paper
Proceedings of eSim 2024: 13th Conference of IBPSA-Canada
Quantifying Airflow Mixing of Diverse Air Distribution Systems Using Taguchi Method and CFD Simulations
Quantifying Airflow Mixing of Diverse Air Distribution Systems Using Taguchi Method and CFD Simulations
Ibrahim Reda, Dahai Qi, Liangzhu Leon Wang, Theodore Stathopoulos, Andreas AthienitisUniversité de SherbrookeAbstract: A novel modified decay method (MDM) has been developed to accurately estimate air change rates within non-uniformly mixed airspaces, relying on a proposed uniformity index (Ui). However, the MDM's applicability has yet to be extended and to further advance its applicability, the Ui values should be quantified for various air distribution systems. Therefore, instead of modeling 700 CFD runs, only 27 simulated scenarios were conducted using the Taguchi method, covering the effect of six ventilation design parameters at three levels on airflow mixing. These factors are airflow direction, layout and shape of air terminals, air change rate, inlet temperature, and source location. Findings showed that the source location strongly affects airflow mixing by 83%, followed by the air change rate (inlet velocity) by 7%, and the third is the inlet temperature by 5%. Tabulated values of Ui were generated for various air-distribution systems to extend the applicability of the MDM. Keywords: Airflow mixing, CFD, Decay method, Uniformity index, Air distribution system, Taguchi method.Paper:![]()