Conference Paper
Proceedings of eSim 2024: 13th Conference of IBPSA-Canada
Characterization of Open Plenum Air Return Operation based on Field Data
Characterization of Open Plenum Air Return Operation based on Field Data
Sabato Leo, Sarah R. Haines, Helen StoppsToronto Metropolitan UniversityAbstract: Open plenum air return systems are prevalent in many commercial and institutional buildings. Despite their widespread use, there is limited information on how well open-plenum systems perform in real-world conditions, and potential operational challenges remain poorly understood. This paper presents the findings of a two-week field study conducted in a 1990s 17-storey office building located in Hamilton, Ontario. During the study, data on the differential pressure between the ceiling plenum and conditioned space as well as between the mechanical room and air handler filters, were collected from two test floors. This data was analysed to explore variations in return airflow, and how external weather factors can affect the indoor differential pressure. It was determined that there is a measurable difference between the 4th and 15th floors’ zone-to-plenum differential pressure under varying conditions. Air handling unit operation, however, was observed to have a minimal impact on zone-to-plenum differential pressures on each floor. Keywords: Open Plenum Air Return, Depressurized Plenum Space, Differential PressurePaper:![]()