Energy and Economic Analysis of an Ice-Storage System for an Office Building Using the Time of Use Tariffs for a Major Canadian Electric Utility

Kamel Haddad, Sara Gilani, Ali Syed
Natural Resources Canada

Abstract: A baseline medium office building archetype model is used to assess the energy, peak reduction, and economic potential of an ice-storage system using time of use tariffs for Toronto Hydro. The results show that this mature technology can effectively reduce peak electricity during on-peak periods, and it has a small effect on the cooling related electricity consumption. However, it is also found that total electricity cost with ice storage deployed during on-peak periods is higher with the time of use tariffs than the base case with a Tired tariff. As a result, utilities such as Toronto Hydro need to better tailor their time of use tariff structures to enhance the financial performance of ice-storage systems so they can be more widely adopted as the electrification of buildings increases.
Keywords: ice storage; peak shaving; electricity tariff; cooling load; demand charge