Conference Paper

Proceedings of eSim 2024: 13th Conference of IBPSA-Canada

     

Evaluation of 222 nm vs 254 nm Lamps for In-duct UVGI Air Disinfection: Irradiance Characterization, Inactivation Performance, and Environmental Implications

Jay Patel, Lexuan Zhong
University of Alberta

Abstract: Challenges remain in characterizing the in-duct irradiance distribution of UVC lamps with air parameters. This study experimentally characterizes irradiance of 222 nm & 254 nm lamps in a conduit using the 9-point average method. Irradiance is measured from all six sides at each point, and a correction factor is proposed to adjust for the overlapped measuring ranges of a spectrometer. The output of the mercury lamp increases by 18% with a rise in air temperature (25°C to 35°C) and decreases by 21% with increased air velocities (0.5 m/s to 2 m/s). In contrast, the excimer lamp shows minimal output change with air parameters. Relative humidity variations (25% to 60%) did not affect the output of any lamp. While the excimer lamp operation in stagnant air leads to substantial ozone generation, the total volatile organic compound levels exhibit minimal change. Finally, UVGI experiments targeting E. coli inactivation efficiency are conducted for both lamps, suggesting 254 nm as a more cost-effective & sustainable solution in duct applications.
Keywords: UVGI In-duct air Disinfection, 222 nm Vs 254 nm, Irradiance, Indoor Air Quality, Bioaerosol
Paper: