Conference Paper
Proceedings of SimBuild Conference 2024
Unveiling the Role of Deployment in the Performance of ASHRAE Guideline 36
Unveiling the Role of Deployment in the Performance of ASHRAE Guideline 36
Sen Huang, Yeobeom Yoon, Piljae Im, Helia Zandi, Jamie LianOak Ridge National Laboratory, United States of AmericaAbstract: This paper presents a simulation-based assessment on how the deployment of ASHRAE Guideline 36: High-Performance Sequences of Operation for HVAC (G36) impacts the energy performance of G36. In this assessment, an EnergyPlus model and a control sequence in G36 are co-simulated. This EnergyPlus model represents a variable air volume system that serves Oak Ridge National Laboratory’s Flexible Research Platform 2 Building. When performing the assessment, we consider six cases, to represent various deployments. In Case 1 and 2, ideal and poor local control loops (LCLs) are considered, respectively. In Case 3 and 4, ideal LCLs with positive and negative sensor bias are considered, respectively. In Case 5 and 6, poor LCLs with positive and negative sensor bias are considered, respectively. Those assessment results suggests 1C sensor bias leads to 2.5 time changes in the energy savings from G36. They also reveal that the control performance of LCL result in 2.3 time differences in the peak power. Keywords: ASHRAE Guideline 36, deployment, volttron, simulation-based control assessment, EnergyPlusPages: 679 - 685 Paper:![]()