	author = {Sungkyun Jung and  Yeoboem Yoon and  Piljae Im},
	title  = {Assessing the Impact of Variable Air Volume Box Damper Stuck Faults Using a Building Automation System and Building Energy Simulation Model},
	booktitle = {Proceedings of SimBuild Conference 2024},
	volume  = {11},
	isbn = {},
	address  = {Denver, Colorado},
	series  = {IBPSA-USA Building Simulation Conference},
	pages = {790--799},
	abstract = {The study examines the impact of variable air volume (VAV) damper stuck faults on the system operation, building indoor conditions, and reheating energy consumption. This study includes both experimental and simulation studies for five test scenarios, including a fault-free scenario. We implemented VAV damper stuck fault through the building automation system (BAS). Results show that a damper stuck in a high opening position (60% damper opening) results in supplying an excessive amount of cold air from the rooftop unit (RTU) to the conditioned zone, increasing reheating energy consumption. The results of this research can serve as a foundational resource for developing fault detection algorithms.},